by Alan S. Brown, Associate Editor
|
back in 1965, Intel
Corp. cofounder Gordon Moore predicted that manufacturers could shrink
electronics fast enough to double the number of transistors on a chip
every two years.
Moore's Law got it about right. Over the past 40 years, manufacturers
have boosted the number of transistors on computer processors from dozens
to hundreds of millions. Today's electronics are smaller, faster,
and far more powerful than those of just a few years ago.
They are also much hotter, quadrupling between 1992 and 2001. Granted,
your desktop computer will not warm your hands on an icy winter morning.
But the electronics in data centers are another story altogether.
Data centers are rooms that house the computer hardware that runs the
software, communications, and databases that glue together large enterprises.
Not that long ago, most data centers were chilled rooms housing large
mainframe computers. Today, those mainframes have given way to microprocessor-based
servers, PC-size computers designed to network into powerful computer
arrays.
|
|
| Electronics have grown much hotter
over the past decade, making cooling a top priority in data centers
like the one pictured on facing page. To keep equipment cool, IBM
routes air conditioning directly into server racks like the one below. |
 |
A typical data center consists of row after row of computer racks. Each
rack stands 6 or 7 feet tall and could easily fit about 40 pizza box-shape
servers and even more of those servers called blades, stripped to their
essential circuit boards.
That, at least, is the theory. Unfortunately, servers generate far too
much heat to fill a rack to capacity. While each individual server actually
runs far cooler than the old mainframe did, stacking them atop one another
in a refrigerator-size enclosed space could produce enough heat to melt
the solder off the boards.
That is why most racks hold far fewer servers than their maximum capacity.
According to Steve Sams, vice president of site and facilities services
for IBM Global Technology Services, a fully loaded rack generates about
32 kilomatts thermal.
Yet when the Uptime Institute Inc., an information technology reliability
organization based in Santa Fe, N.M., surveyed 19 computer rooms measuring
a total of 204,000 square feet (slightly larger than four football fields),
it found that, in practice, hardware on the average rack generated only
2.1 kW of heat.
According to Uptime, most data rooms struggled to handle even that. Hot
spots occurred even though the average computer room used 2.6 times more
cooling capacity than optimally required for the heat load. One room actually
had 25 percent hot spots despite running 10 times more cooling capacity
than required. In fact, one out of every 10 servers measured ran hotter
than its published reliability guidelines. Some ran at 100°F. For
every 18 degrees above 70°F, reliability declines by 50 percent.
Where Has All the Cooling
Gone?
No wonder excessive heat was the No. 1 facilities concern among data center
managers, according to a recent survey by Gartner Group, a well-known
IT consultancy in Stamford, Conn. "Power and cooling will be a
top-three issue with all chief information officers in the next six to
12 months," Gartner consultant Michael Bell said.
It's not as if data room cooling systems lack sophistication. They
are, in essence, large refrigerators. Most of them circulate cool air
under raised floors, then push it through floor vents aimed at the racks.
The cool air passes over the hot servers, then exits the room as warmed
air through returns in the side walls and mixes with cold air as it goes.
The problem, says Uptime, is that only 28 percent of the chilled air actually
reaches the computer equipment. The remaining 72 percent bypasses the
servers entirely. More than half that amount escapes from unsealed cable
holes and conduits. Another 14 percent exits floor vents facing away from
the hot racks rather than toward them. More air is obstructed by the snake's
nest of wires under the floor. A full 10 percent of air conditioning equipment
fails without notifying operators.
In addition, hot air exiting the racks mixes with cool room air, lowering
room temperatures. Most rooms are dotted with hot spots where temperatures
exceed requirements. Servers generally respond to such high temperatures
by throttling back on power consumption, which reduces performance.
In the past, data room managers simply threw more cooling at hot rooms
or moved their servers to larger rooms. Higher power costs and tighter
budgets have made these options more painful today.
Unfortunately, electronics keep getting hotter. Between 1992 and 2001,
the heat load per square foot of server rose about 18 percent annually,
more than quadrupling to 1,100 watts per square foot. Although the rate
of heat buildup has slowed, it remains in double digits and is not expected
to level off until 2010. Correcting air bypass problems may solve some
of today's problems, but it won't enable users to run denser
racks in the future.
Ben Steinberg, a staff applications engineer at American Power Conversion
Corp. of Newport, R.I., agrees. "About 90 percent of new data centers
run racks at only 2 to 5 kW," he said. "Two of those racks
together use as much power as a home oven. And as soon as you turn on
the switch, you need at least as much power to keep them cool."
Solving the Problem
Multiply this by dozens or even hundreds of racks, and it is easy to see
why rising electronics temperatures are overwhelming cooling systems and
utility budgets. APC, better known for backup power supplies, thinks it
has a solution that is simplicity itself: Isolate the problem.
The company starts by abandoning the old cooling architecture. Instead
of running cold air up from the floor, APC supplies cold air from rack-size
towers mounted along each row. It then monitors server temperatures, adjusting
each individual air conditioner tower to achieve optimal cooling. Such
localized cooling is so efficient that users can boost server rack power
to 18 kWnearly nine times the average found by Uptime.
A second innovation adds enough cooling capacity to handle a 30 kW bank
of servers, APC said. APC encloses the exhaust end of two adjacent rows
of racks under a single hood. According to the company, instead of releasing
hot air into the room, where it can produce hot spots, the system contains
hot air and carries it away.
APC is not alone in trying to cool data centers. Just about every provider
of server racks and IT services wants a piece of the lucrative $25 billion
data center renovation, expansion, and relocation market. Cooling and
power are a big part of this business. In fact, market researcher International
Data Group Inc. of Boston predicts that data center spending on these
products will surpass money invested in servers within the next year or
two.
 |
| APC encloses racks to remove hot
air efficiently (above). A typical high-performance data center (below),
in which IBM has a new racking system. |
 |
IBM believes even the largest, most sophisticated data center managers
need help with cooling. "Ten and fifteen years ago, we all built
data centers using rules of thumb," Sams said. "At the time,
we were generating only 1 to 3 kW of heat in a rack-size space. Today,
it's 20 kW and maxes out at 32 kW, and those rules of thumb have
no value. We have to be cognizant of what we put where or we will melt
the servers in the rack."
Like APC, IBM also has a new racking system capable of handling 20 to
25 kW heat loads. Instead of adding in-line air conditioners, IBM redirects
the data center's air conditioning through the rack itself. Like
APC, it encloses its racks with a roof, but unlike APC it uses a cold
rather than hot center aisle and exhausts the heated air into the data
center. "We believe the design is 40 to 50 percent better than
conventional racking, and we are going to run tests to compare it with
APC," Sams said.
Installation calls for running new air conditioning vents under the raised
data center floor. This space is usually filled with a snake's
nest of unused electrical cables from previous room configurations. Removing
old cables to make room for the vents eliminates airflow obstructions
and also adds to the center's data efficiency, according to Sams.
IBM also removes heat with a water-cooled heat exchanger attached to the
back of a rack. "It looks like an auto radiator and eliminates
about 50 percent of the heat," Sams said. "We used it at
Georgia Tech's high-performance computer center to enable a non-state-of-the-art
data center to support state-of-the-art technology."
In addition, IBM provides power management software that enables IT managers
to adjust power and heat output. "They can power down based on
workload, or move workload to environments that are not effectively using
the power and cooling capacity that they have," Sams said. "It
lets them spread the work around so you don't need extra cooling
or build up hot spots."
For IT departments seeking to cut power bills and stretch existing assets,
such solutions can't come too soon.